Tangit FP300 Fire Protection Mortar

Non-shrinking, cement based fire resistant mortar.


PROPERTIES

  • Fire resistant class A1 acc. DIN 4102
  • Mortar group MG III
  • Complies with DIN 4102, MLAR 2005/LAR/RbALei, NEN 1366-3
  • Non shrinking 
  • For the fluid AND stable working conditions
  • Pumpable
  • Processing time 60 – 120 Minutes 
  •  Resistant to aging and rotting

TESTING AND APPROVAL
Complies with EN 1366-3, DIN 4102, MLAR2005/LAR/RbALei, NEN 1366-3

APPLICATION SCOPE
For fire resistant sealing and fixing of fire dumpers, air ducts and fire protection doors.


TECHNICAL INFORMATION
Colour:   grey (mixed)
Density:   approx. 1.69 kg/dm3
Min application temperature:  +5ºC
Handling time:   60 - 120 minutes (at 20oC)
Compressive strength:  23,2 N/mm2
Flexural strength:   7.2 N/mm2
Adhesive shear strength: 0,69 N/mm2