Tangit

Pipe Adhesives & Cleaners

Thread Sealants

House Service Line Fixation

Fire Protection

Advantages

Fire Protection Basics

REFA Time Efficiency Study

System Comparison

Application & Installation

Products

Downloads

Tangit FP100 Fire Protection 1C Foam

Single component acrylic sealant for fire resistant and smoke tight closing of linear building joints in walls and ceilings acc. EN 1366-4


PROPERTIES

  • Fire resistant and smoke tight from EI60 up to EI240
  • Tested according EN 1366-4
  • Fire resistant class B acc. EN13501 and B1 acc.DIN4102
  • High yield of approx. 45 litres per can
  • Quick curing: teck-free after 5-8 minutes, can be cut after approx. 7-10 minutes
  • Additional thermal and acoustic protection
  • Simple, fast and clean handling
  • Free of propellant

TESTING AND APPROVAL
Tested and certified according EN 1366-4

APPLICATION SCOPE
For fire-resistant and smoke-tight closing of linear joints  ≤45mm in walls and ceilings according EN 1366-4.


TECHNICAL INFORMATION
Material: 1c polyurethane
Color: light green
Yield (750 ml): up to 45 litres
Bulk density: approx. 15 kg/m3
Cell-structure: medium
 Tack-free: 5-8 minutes
 Can be cut after (20 mm bead): 7-10 minutes
 Stability load bearing (20 mm bead): after approx. 12 hours
 Minimum working temperature (Can, application surfaces): + 5oC
 Maximum working temperature (Can, application surfaces) : +30oC
 Optimum working temperature (Can, application surfaces): +20oC
 Tensile strength (DIN 53430): 8-10 N/cm2
 Elongation at tension (DIN 53430): approx. 18 %
 Shear strength (DIN 53427): 4-5 N/cm2
 Compressive strength at 10% stress (DIN 53421): 2-3 N/cm2
 Temperature resistance of the cured bead Long-term: -40oC to + 80oC
determined at +23oC, 50 % relative air humidity)



Downloads

Technical Data Sheet