Tangit

Pipe Adhesives & Cleaners

Thread Sealants

House Service Line Fixation

Fire Protection

Advantages

Fire Protection Basics

REFA Time Efficiency Study

System Comparison

Application & Installation

Products

Downloads

Tangit FP450 Fire Protection Mastic

Intumescent single component mastic for fire resistant cable penetrations in combination with Tangit FP550.


PROPERTIES

  • Fire-resistant and smoke-tight up to EI90 / S90
  • Fire protection classification B1/B2 acc. DIN4102
  • Complies with EN1366-3, DIN 4102, NEN 1366-3
  • Intumescent when heated
  • Simple, fast and clean handling
  • Free of halogens, plasticizers and organic solvents
  • Resistant to aging and rotting
  • TESTING AND APPROVAL
  • Complies with EN 1366-3, DIN 4102, NEN 1366-3
  • ABZ: Z-19.11-1793

APPLICATION SCOPE
Fire-resistant intumescent mastic for electrical cables (diameter ≤ 32mm),
cable bundles and cable trays in walls and ceilings. Part of the Tangit Fire
Protection System for electrical cable penetrations (in combination with FP 550 and
FP 800).

 


TECHNICAL INFORMATION
Material: acrylic polymer dispersion  with fire protection additives
Colour: red-brown
pH value: pH 7.0 - 8.0
Solid matter content: approx. 80%
Intumescence factor when heated: 10 times
Density: approx. 1.35 g/cm3
Skin formation time: approx. 7 Min.
Hardness Shore A: approx. 45
Application temperature: +5oC to +40oC
opt is +20oC to +25oC
Temperature stability:                   -20oC to +80oC



Downloads

Technical Data Sheet